Please use this identifier to cite or link to this item: https://doi.org/10.1109/TIE.2007.894701
DC FieldValue
dc.titleAnalysis and design of Iterative learning Control strategies for UPS Inverters
dc.contributor.authorDeng, H.
dc.contributor.authorOruganti, R.
dc.contributor.authorSrinivasans, D.
dc.date.accessioned2014-06-19T03:00:00Z
dc.date.available2014-06-19T03:00:00Z
dc.date.issued2007-06
dc.identifier.citationDeng, H., Oruganti, R., Srinivasans, D. (2007-06). Analysis and design of Iterative learning Control strategies for UPS Inverters. IEEE Transactions on Industrial Electronics 54 (3) : 1739-1751. ScholarBank@NUS Repository. https://doi.org/10.1109/TIE.2007.894701
dc.identifier.issn02780046
dc.identifier.urihttp://scholarbank.nus.edu.sg/handle/10635/69379
dc.description.abstractIn this paper, two iterative-learning-based control methods for uninterruptible power system (UPS) inverters, viz., direct iterative learning controller (direct ILC) and hybrid iterative learning controller (hybrid ILC), are proposed. In both methods, a zero-phase filter that is designed in the frequency domain is applied in order to provide compensation for the resonant peak in the system model to ensure error convergence. Furthermore, a forgetting factor is introduced in both control algorithms to increase the robustness of the scheme against measurement noise, initialization error, and/or variation of system dynamics due to any parameter drift. In the direct ILC method, ILC is combined with the feedforward of the reference to improve dynamic performance. This method is shown to be capable of achieving very high steady-state performance although its dynamic response was not very good. In the hybrid ILC method, ILC is combined with a proportional-derivative controller aside from the reference feedforward to improve the dynamic response further. Experimental results show that both proposed controllers can achieve very low total harmonic distortion and fast error convergence under different loads while using only one sensor. The proposed direct ILC is an effective solution for UPS products where high-quality steady-state output voltage is more important than fast dynamic response, while hybrid ILC can result in excellent steady-state performance with a more improved dynamic response than direct ILC. © 2007 IEEE.
dc.description.urihttp://libproxy1.nus.edu.sg/login?url=http://dx.doi.org/10.1109/TIE.2007.894701
dc.sourceScopus
dc.subjectDigital control
dc.subjectInverters
dc.subjectIterative methods
dc.subjectUninterruptible power systems (UPSS)
dc.typeConference Paper
dc.contributor.departmentELECTRICAL & COMPUTER ENGINEERING
dc.description.doi10.1109/TIE.2007.894701
dc.description.sourcetitleIEEE Transactions on Industrial Electronics
dc.description.volume54
dc.description.issue3
dc.description.page1739-1751
dc.description.codenITIED
dc.identifier.isiut000247203000046
Appears in Collections:Staff Publications

Show simple item record
Files in This Item:
There are no files associated with this item.

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.