Please use this identifier to cite or link to this item:
https://scholarbank.nus.edu.sg/handle/10635/62040
Title: | Digital distance relaying algorithm for first-zone protection for parallel transmission lines | Authors: | Liao, Y. Elangovan, S. |
Keywords: | Algorithm Distance protection Parallel transmission lines |
Issue Date: | 1998 | Citation: | Liao, Y.,Elangovan, S. (1998). Digital distance relaying algorithm for first-zone protection for parallel transmission lines. IEE Proceedings: Generation, Transmission and Distribution 145 (5) : 531-536. ScholarBank@NUS Repository. | Abstract: | The paper proposes a new digital distance relaying algorithm for first-zone protection for parallel transmission lines. The new method uses data from one end of the protected parallel lines to calculate the fault distance. It is shown that the new method is independent of fault resistance, remote infeed and source impedances. Extensive simulation studies using EMTP have verified that this approach can obtain a highly accurate fault distance estimation within one cycle after fault inception and hence is very much suitable for digital distance protection for parallel lines. Applications of this method for fault location are also presented. © IEE, 1998. | Source Title: | IEE Proceedings: Generation, Transmission and Distribution | URI: | http://scholarbank.nus.edu.sg/handle/10635/62040 | ISSN: | 13502360 |
Appears in Collections: | Staff Publications |
Show full item record
Files in This Item:
There are no files associated with this item.
Google ScholarTM
Check
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.