Please use this identifier to cite or link to this item: https://doi.org/10.1016/j.ijheatmasstransfer.2012.12.055
DC FieldValue
dc.titleEntropy generation analysis of an adsorption cooling cycle
dc.contributor.authorThu, K.
dc.contributor.authorKim, Y.-D.
dc.contributor.authorMyat, A.
dc.contributor.authorChun, W.G.
dc.contributor.authorNg, K.C.
dc.date.accessioned2014-06-17T06:20:23Z
dc.date.available2014-06-17T06:20:23Z
dc.date.issued2013
dc.identifier.citationThu, K., Kim, Y.-D., Myat, A., Chun, W.G., Ng, K.C. (2013). Entropy generation analysis of an adsorption cooling cycle. International Journal of Heat and Mass Transfer 60 (1) : 143-150. ScholarBank@NUS Repository. https://doi.org/10.1016/j.ijheatmasstransfer.2012.12.055
dc.identifier.issn00179310
dc.identifier.urihttp://scholarbank.nus.edu.sg/handle/10635/60199
dc.description.abstractThis paper discusses the analysis of an adsorption (AD) chiller using system entropy generation as a thermodynamic framework for evaluating total dissipative losses that occurred in a batch-operated AD cycle. The study focuses on an adsorption cycle operating at heat source temperatures ranging from 60 to 85 °C, whilst the chilled water inlet temperature is fixed at 12.5 °C,-a temperature of chilled water deemed useful for dehumidification and cooling. The total entropy generation model examines the processes of key components of the AD chiller such as the heat and mass transfer, flushing and de-superheating of liquid refrigerant. The following key findings are observed: (i) The cycle entropy generation increases with the increase in the heat source temperature (10.8 to 46.2 W/K) and the largest share of entropy generation or rate of energy dissipation occurs at the adsorption process, (ii) the second highest energy rate dissipation is the desorption process, (iii) the remaining energy dissipation rates are the evaporation and condensation processes, respectively. Some of the noteworthy highlights from the study are the inevitable but significant dissipative losses found in switching processes of adsorption-desorption and vice versa, as well as the de-superheating of warm condensate that is refluxed at non-thermal equilibrium conditions from the condenser to the evaporator for the completion of the refrigeration cycle. © 2012 Elsevier Ltd. All rights reserved.
dc.description.urihttp://libproxy1.nus.edu.sg/login?url=http://dx.doi.org/10.1016/j.ijheatmasstransfer.2012.12.055
dc.sourceScopus
dc.subjectAdsorption
dc.subjectAdsorption chiller
dc.subjectEntropy generation
dc.subjectSecond law analysis
dc.subjectSilica gel
dc.typeArticle
dc.contributor.departmentMECHANICAL ENGINEERING
dc.description.doi10.1016/j.ijheatmasstransfer.2012.12.055
dc.description.sourcetitleInternational Journal of Heat and Mass Transfer
dc.description.volume60
dc.description.issue1
dc.description.page143-150
dc.description.codenIJHMA
dc.identifier.isiut000317534500018