Please use this identifier to cite or link to this item: https://doi.org/10.3390/en6094551
DC FieldValue
dc.titleBubbleZERO-design, construction and operation of a transportable research laboratory for low exergy building system evaluation in the tropics
dc.contributor.authorBruelisauer, M.
dc.contributor.authorChen, K.W.
dc.contributor.authorIyengar, R.
dc.contributor.authorLeibundgut, H.
dc.contributor.authorLi, C.
dc.contributor.authorLi, M.
dc.contributor.authorMast, M.
dc.contributor.authorMeggers, F.
dc.contributor.authorMiller, C.
dc.contributor.authorRossi, D.
dc.contributor.authorSaber, E.M.
dc.contributor.authorSchlueter, A.
dc.contributor.authorTham, K.W.
dc.date.accessioned2014-12-01T08:23:18Z
dc.date.available2014-12-01T08:23:18Z
dc.date.issued2013
dc.identifier.citationBruelisauer, M., Chen, K.W., Iyengar, R., Leibundgut, H., Li, C., Li, M., Mast, M., Meggers, F., Miller, C., Rossi, D., Saber, E.M., Schlueter, A., Tham, K.W. (2013). BubbleZERO-design, construction and operation of a transportable research laboratory for low exergy building system evaluation in the tropics. Energies 6 (9) : 4551-4571. ScholarBank@NUS Repository. https://doi.org/10.3390/en6094551
dc.identifier.issn19961073
dc.identifier.urihttp://scholarbank.nus.edu.sg/handle/10635/113976
dc.description.abstractWe present the design, construction and operation of a novel building systems laboratory, the BubbleZERO-Zero Emission Research Operation. Our objective was to design a space to evaluate the performance of Swiss-developed low exergy building systems in the tropical climate of Singapore using an integrated design approach. The method we employed for evaluation in the tropics was to design and build a test bed out of the shipping containers that transported the prototype low exergy systems from Switzerland to Singapore. This approach resulted in a novel laboratory environment containing radiant cooling panels and decentralized air supply, along with a self-shading, inflated "bubble" skin, experimental low emissivity (LowE) glazing, LED lighting, wireless sensors and distributed control. The laboratory evaluates and demonstrates for the first time in Singapore an integrated high-temperature cooling system with separate demand-controlled ventilation adapted for the tropics. It is a functional lab testing system in real tropical conditions. As such, the results showing the ability to mitigate the risk of condensation by maintaining a dew point below 18 °C by the separate decentralized ventilation are significant and necessary for potential future implementation in buildings. In addition, the control system provides new proof of concept for distributed wireless sensors and control for reliable automation of the systems. These key results are presented along with the integrated design process and real-life tropical operation of the laboratory. © 2013 by the authors.
dc.description.urihttp://libproxy1.nus.edu.sg/login?url=http://dx.doi.org/10.3390/en6094551
dc.sourceScopus
dc.subjectBuildings
dc.subjectDistributed systems
dc.subjectEnergy efficiency
dc.subjectExergy
dc.subjectLaboratory
dc.subjectPrototype
dc.subjectRadiant cooling
dc.subjectTropical climate
dc.subjectZero emission
dc.typeArticle
dc.contributor.departmentBUILDING
dc.description.doi10.3390/en6094551
dc.description.sourcetitleEnergies
dc.description.volume6
dc.description.issue9
dc.description.page4551-4571
dc.identifier.isiut000330285200012
Appears in Collections:Staff Publications