Please use this identifier to cite or link to this item: https://scholarbank.nus.edu.sg/handle/10635/72666
Title: GROUND-FAULT PROTECTION SCHEME FOR AN EMERGENCY OR STANDBY POWER SYSTEM WITH MULTIPLE NEUTRAL-TO-GROUND CONNECTIONS.
Authors: Liew, A.C. 
Issue Date: 1986
Citation: Liew, A.C. (1986). GROUND-FAULT PROTECTION SCHEME FOR AN EMERGENCY OR STANDBY POWER SYSTEM WITH MULTIPLE NEUTRAL-TO-GROUND CONNECTIONS.. Conference Record - IAS Annual Meeting (IEEE Industry Applications Society) : 982-985. ScholarBank@NUS Repository.
Abstract: Problems associated with improper sensing of ground faults and unbalanced currents in an electrical system with multiple neutral-to-ground connections are reviewed. A special ground-fault sensing scheme is presented to overcome these problems. The system proposed is especially applicable in the case where an emergency standby generator backfeeds into a transformer and supplies its local load.
Source Title: Conference Record - IAS Annual Meeting (IEEE Industry Applications Society)
URI: http://scholarbank.nus.edu.sg/handle/10635/72666
ISSN: 01972618