Title: Unsynchronised two-terminal transmission-line fault-location without using line parameters
Authors: Liao, Y.
Elangovan, S. 
Issue Date: 2006
Citation: Liao, Y., Elangovan, S. (2006). Unsynchronised two-terminal transmission-line fault-location without using line parameters. IEE Proceedings: Generation, Transmission and Distribution 153 (6) : 639-643. ScholarBank@NUS Repository. https://doi.org/10.1049/ip-gtd:20060026
Abstract: The paper presents a new two-terminal transmission-line fault-location algorithm without requiring line parameters. The voltage and current measurements at both ends of a transmission line during a fault are assumed to be available and no synchronisation of the data is required. The proposed algorithm is suitable for estimating the location of asymmetric faults on a line when line parameters are not available. Evaluation studies using both simulated and field data are reported. © The Institution of Engineering and Technology 2006.
Source Title: IEE Proceedings: Generation, Transmission and Distribution
URI: http://scholarbank.nus.edu.sg/handle/10635/57755
ISSN: 13502360
DOI: 10.1049/ip-gtd:20060026