dc.titleRelay-based on-line monitoring procedures for 2 × 2 and 3 × 3 multiloop control systems
dc.contributor.authorJu, J.
dc.date.accessioned2014-10-09T08:20:54Z
dc.date.available2014-10-09T08:20:54Z
dc.date.issued1997
dc.identifier.citationJu, J. (1997). Relay-based on-line monitoring procedures for 2 × 2 and 3 × 3 multiloop control systems. Industrial and Engineering Chemistry Research 36 (6) : 2225-2230. ScholarBank@NUS Repository.
dc.identifier.issn08885885
dc.identifier.urihttp://scholarbank.nus.edu.sg/handle/10635/91675
dc.description.abstractA monitoring procedure is proposed to identify on-line the maximum closed-loop log modulus, Lc,max, for multiloop control systems. Lc,max is considered because it measures the robustness of the control systems and thereby can indicate the appropriateness of controller design with respect to the current operating conditions. The proposed method identifies Lc,max via relay feedback experiments without requiring a priori information of process conditions. This procedure is applied to both linear systems and nonlinear systems. The results show that the proposed method is efficient and accurate in on-line identification of Lc,max. © 1997 American Chemical Society.
dc.sourceScopus
dc.typeArticle
dc.contributor.departmentCHEMICAL ENGINEERING
dc.description.sourcetitleIndustrial and Engineering Chemistry Research
dc.description.volume36
dc.description.issue6
dc.description.page2225-2230
dc.description.codenIECRE
dc.identifier.isiutNOT_IN_WOS
Appears in Collections:Staff Publications

Show simple item record
Files in This Item:
There are no files associated with this item.

Google ScholarTM

Check


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.