dc.titlePerformance evaluation of the coupling of a desktop personalized ventilation air terminal device and desk mounted fans
dc.contributor.authorTham, K.W.
dc.contributor.authorPantelic, J.
dc.date.accessioned2013-10-14T04:40:29Z
dc.date.available2013-10-14T04:40:29Z
dc.date.issued2010
dc.identifier.citationTham, K.W., Pantelic, J. (2010). Performance evaluation of the coupling of a desktop personalized ventilation air terminal device and desk mounted fans. Building and Environment 45 (9) : 1941-1950. ScholarBank@NUS Repository. https://doi.org/10.1016/j.buildenv.2010.01.019
dc.identifier.issn03601323
dc.identifier.urihttp://scholarbank.nus.edu.sg/handle/10635/45793
dc.description.abstractThe performance of a coupled system of the Desktop Personalized Ventilation Air Terminal Device (DPV ATD) and desk mounted fans (DMF) was examined in a field environmental chamber. Cooling effect was evaluated using manikin-based equivalent temperature (Teq,), of each of the 26 body segments of a breathing thermal manikin (BTM) and personal exposure effectiveness (PEE) was used as an indicator for effectiveness of ventilation. Computational fluid dynamics (CFD) was used to examine the velocity field generated around BTM to provide better understanding of the relationship between air patterns generated and convective cooling effect on each of the body segments produced by DPV ATD coupled with DMF. Four different positions of DPV ATD were examined: two positions each in front and on the side of the BTM. Measurements were conducted at ambient temperature of 26°C and PV air temperature of 23°C at a flow rate of 10. L/s. The results indicate that coupling of DPV ATD and DMF distributes cooling more uniformly across BTM surfaces and therefore has the potential to reduce risk of draft discomfort as compared to usage of DPV ATD alone. Personalized exposure effectiveness was increased in 3 of the positions examined when the coupled system was used. © 2010 Elsevier Ltd.
dc.description.urihttp://libproxy1.nus.edu.sg/login?url=http://dx.doi.org/10.1016/j.buildenv.2010.01.019
dc.sourceScopus
dc.subjectComputational fluid dynamics
dc.subjectDesk mounted fans
dc.subjectDesktop personalized ventilation
dc.subjectManikin-based equivalent temperature
dc.subjectPersonal exposure effectiveness
dc.subjectThermal manikin
dc.typeArticle
dc.contributor.departmentBUILDING
dc.description.doi10.1016/j.buildenv.2010.01.019
dc.description.sourcetitleBuilding and Environment
dc.description.volume45
dc.description.issue9
dc.description.page1941-1950
dc.description.codenBUEND
dc.identifier.isiut000278571600006
Appears in Collections:Staff Publications

Show simple item record
Files in This Item:
There are no files associated with this item.

SCOPUSTM   
Citations

23
checked on Jan 27, 2020

WEB OF SCIENCETM
Citations

21
checked on Jan 27, 2020

Page view(s)

101
checked on Dec 30, 2019

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.