Please use this identifier to cite or link to this item: https://doi.org/10.1115/HT2005-72226
Title: Experimental investigation of an Electro-adsorption chiller
Authors: Choon, N.K. 
Xiaolin, W. 
Lizhen, G.
Anutosh, C. 
Aye, S.M.
Issue Date: 2005
Citation: Choon, N.K., Xiaolin, W., Lizhen, G., Anutosh, C., Aye, S.M. (2005). Experimental investigation of an Electro-adsorption chiller. Proceedings of the ASME Summer Heat Transfer Conference 1 : 57-60. ScholarBank@NUS Repository. https://doi.org/10.1115/HT2005-72226
Abstract: A comprehensive experiment has been conducted on a novel electro-adsorption chiller (EAC) with a rated cooling capacity of 120 W (uniform heat flux of about 4.7 W/cm2). At these rated conditions, it produces a heating load surface temperature of 23°C, about 10 degree below that of the heating-load temperature. The coefficient of performance (COP) of the prototype EAC is measured to be about 0.84. Copyright © 2005 by ASME.
Source Title: Proceedings of the ASME Summer Heat Transfer Conference
URI: http://scholarbank.nus.edu.sg/handle/10635/85962
ISBN: 0791847314
DOI: 10.1115/HT2005-72226
Appears in Collections:Staff Publications

Show full item record
Files in This Item:
There are no files associated with this item.

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.