Please use this identifier to cite or link to this item: https://doi.org/10.1115/HT2005-72226
Title: Experimental investigation of an Electro-adsorption chiller
Authors: Choon, N.K. 
Xiaolin, W. 
Lizhen, G.
Anutosh, C. 
Aye, S.M.
Issue Date: 2005
Citation: Choon, N.K., Xiaolin, W., Lizhen, G., Anutosh, C., Aye, S.M. (2005). Experimental investigation of an Electro-adsorption chiller. Proceedings of the ASME Summer Heat Transfer Conference 1 : 57-60. ScholarBank@NUS Repository. https://doi.org/10.1115/HT2005-72226
Abstract: A comprehensive experiment has been conducted on a novel electro-adsorption chiller (EAC) with a rated cooling capacity of 120 W (uniform heat flux of about 4.7 W/cm2). At these rated conditions, it produces a heating load surface temperature of 23°C, about 10 degree below that of the heating-load temperature. The coefficient of performance (COP) of the prototype EAC is measured to be about 0.84. Copyright © 2005 by ASME.
Source Title: Proceedings of the ASME Summer Heat Transfer Conference
URI: http://scholarbank.nus.edu.sg/handle/10635/85962
ISBN: 0791847314
DOI: 10.1115/HT2005-72226
Appears in Collections:Staff Publications

Show full item record
Files in This Item:
There are no files associated with this item.

SCOPUSTM   
Citations

2
checked on Jul 14, 2018

Page view(s)

31
checked on Jun 22, 2018

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.