Please use this identifier to cite or link to this item: http://scholarbank.nus.edu.sg/handle/10635/80842
Title: Nuisance trippings of residual current circuit breakers or ground fault protectors of power sources connected to computer and electronic loads
Authors: Liew, A.C. 
Issue Date: Dec-1990
Source: Liew, A.C. (1990-12). Nuisance trippings of residual current circuit breakers or ground fault protectors of power sources connected to computer and electronic loads. Electric Power Systems Research 20 (1) : 23-30. ScholarBank@NUS Repository.
Abstract: Nuisance trippings of residual current circuit breakers (RCCBs) or ground fault protectors (GFPs) are frequently experienced in environments supporting computer and electronic type loads. This paper discusses the causes of these problems and identifies high levels of earth leakage currents through filter capacitors present in the power supply circuits of these loads as a major reason. A new special dedicated earth return scheme used with a special RCCB which can overcome this effect is offered. © 1990.
Source Title: Electric Power Systems Research
URI: http://scholarbank.nus.edu.sg/handle/10635/80842
ISSN: 03787796
Appears in Collections:Staff Publications

Show full item record
Files in This Item:
There are no files associated with this item.

Page view(s)

24
checked on Jan 13, 2018

Google ScholarTM

Check


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.