Abstract: This paper reports our findings from a study in an institutional building complex in Singapore with significant load diversity, aimed at improving the energy efficiency of a conventional chilled water plant (CCWP) during a retrofitting activity. An energy simulation program is used for the evaluation of different energy conservation opportunities, preceded by an initial exploration involving a validation of the computer model with historic energy use through a comparison with actual energy data. The concept of an integrated retrofitting strategy is used that is aimed at optimizing component performance by a combination of different strategies. Retrofitting techniques for an old or conventional chilled water plant that relies on minimization of cooling demands and optimization of equipment can achieve roughly a 47% reduction in yearly energy use over CCWP. A further retrofit of the old equipment with energy efficient chillers and motors with VSD control will yield up to 51% energy conservation.
Source Title: ASHRAE Transactions
URI: http://scholarbank.nus.edu.sg/handle/10635/45948
ISSN: 00012505
Appears in Collections:Staff Publications

Show full item record
Files in This Item:
There are no files associated with this item.

Page view(s)

70
checked on Dec 9, 2017

Google ScholarTM

Check


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.