Please use this identifier to cite or link to this item: https://doi.org/10.1016/j.buildenv.2010.01.019
Title: Performance evaluation of the coupling of a desktop personalized ventilation air terminal device and desk mounted fans
Authors: Tham, K.W. 
Pantelic, J. 
Keywords: Computational fluid dynamics
Desk mounted fans
Desktop personalized ventilation
Manikin-based equivalent temperature
Personal exposure effectiveness
Thermal manikin
Issue Date: 2010
Source: Tham, K.W., Pantelic, J. (2010). Performance evaluation of the coupling of a desktop personalized ventilation air terminal device and desk mounted fans. Building and Environment 45 (9) : 1941-1950. ScholarBank@NUS Repository. https://doi.org/10.1016/j.buildenv.2010.01.019
Abstract: The performance of a coupled system of the Desktop Personalized Ventilation Air Terminal Device (DPV ATD) and desk mounted fans (DMF) was examined in a field environmental chamber. Cooling effect was evaluated using manikin-based equivalent temperature (Teq,), of each of the 26 body segments of a breathing thermal manikin (BTM) and personal exposure effectiveness (PEE) was used as an indicator for effectiveness of ventilation. Computational fluid dynamics (CFD) was used to examine the velocity field generated around BTM to provide better understanding of the relationship between air patterns generated and convective cooling effect on each of the body segments produced by DPV ATD coupled with DMF. Four different positions of DPV ATD were examined: two positions each in front and on the side of the BTM. Measurements were conducted at ambient temperature of 26°C and PV air temperature of 23°C at a flow rate of 10. L/s. The results indicate that coupling of DPV ATD and DMF distributes cooling more uniformly across BTM surfaces and therefore has the potential to reduce risk of draft discomfort as compared to usage of DPV ATD alone. Personalized exposure effectiveness was increased in 3 of the positions examined when the coupled system was used. © 2010 Elsevier Ltd.
Source Title: Building and Environment
URI: http://scholarbank.nus.edu.sg/handle/10635/45793
ISSN: 03601323
DOI: 10.1016/j.buildenv.2010.01.019
Appears in Collections:Staff Publications

Show full item record
Files in This Item:
There are no files associated with this item.

SCOPUSTM   
Citations

16
checked on Dec 13, 2017

WEB OF SCIENCETM
Citations

14
checked on Nov 16, 2017

Page view(s)

70
checked on Dec 10, 2017

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.